Europe Style For Ac Adapter Transformer - Three phase AC Type input reactor – Xinping
Europe Style For Ac Adapter Transformer - Three phase AC Type input reactor – Xinping Detail:
Characteristic
Effectively restrain harmonic current, improve the power factor of the whole machine, effectively restrain the current impact caused by the sudden change of grid voltage and over-voltage, improve the interference of the power supply to other equipment, and improve the unbalanced voltage between power supply phases that is greater than the rated voltage
| Technical Data | |
| Rated Voltage: | 380V/440V |
| Operation Frequency: | 50/60HZ |
| Rated Current: | 3A-1600A |
| Hi-pot Test: | 3.5kV, 60sec |
| Insulation Class: | F or above |
| Reactor Impedance: | 2% |
| Ambient temperature: | -25^ to 401: |
| Protection Category: | I POO |
| Design corresponding to Standards: | GB19212.1-2008 / GB19212.21-2007 /GB1094.6-2011 |
Application Schematic
Outline dimension drawing

|
Type Selection Table |
|||||||
|
|
|
(mH) |
(A) |
m(m) Dimensions 1 |
|||
|
Model |
Power (KW) |
Inductance |
Rated Current |
L |
W |
H |
Installation dimensions E*F |
|
5A |
1.5 |
2.80 |
5 |
160 |
120 |
140 |
80*60 |
|
7A |
2.2 |
2.00 |
7 |
160 |
120 |
140 |
80*60 |
|
10A |
3.7 |
1.40 |
10 |
160 |
120 |
140 |
80*60 |
|
ISA |
5.5 |
0.93 |
15 |
160 |
120 |
140 |
80*60 |
|
20A |
7.5 |
0.70 |
20 |
160 |
120 |
140 |
80*60 |
|
30A |
11 |
0.47 |
30 |
160 |
120 |
140 |
80*60 |
|
40A |
15 |
0.35 |
40 |
160 |
120 |
140 |
80*60 |
|
50A |
18.5 |
0.28 |
50 |
160 |
130 |
140 |
80*75 |
|
60A |
22 |
0.24 |
60 |
160 |
140 |
140 |
80*85 |
|
80A |
30 |
0.17 |
80 |
190 |
150 |
160 |
80*85 |
|
90A |
37 |
0.16 |
90 |
190 |
150 |
160 |
80*85 |
|
120A |
45 |
0.12 |
120 |
190 |
150 |
160 |
80*95 |
|
150A |
55 |
0.09 |
150 |
225 |
160 |
190 |
120*85 |
|
200A |
75 |
0.07 |
200 |
225 |
160 |
220 |
120*85 |
|
220A |
90 |
0.064 |
220 |
225 |
170 |
220 |
120*95 |
|
250A |
110 |
0.056 |
250 |
225 |
180 |
220 |
120*95 |
|
290A |
132 |
0.047 |
290 |
260 |
160 |
250 |
135*85 |
|
330A |
160 |
0.042 |
330 |
260 |
170 |
250 |
135*95 |
|
390A |
185 |
0.036 |
390 |
260 |
170 |
250 |
135*95 |
|
440A |
200 |
0.032 |
440 |
260 |
170 |
250 |
135*95 |
|
490A |
220 |
0.028 |
490 |
260 |
180 |
250 |
135*95 |
|
540A |
250 |
0.025 |
540 |
290 |
200 |
310 |
135*95 |
|
600A |
280 |
0.023 |
600 |
290 |
210 |
310 |
135*95 |
|
700A |
315 |
0.021 |
700 |
290 |
210 |
310 |
135*105 |
|
800A |
350 |
0.018 |
800 |
290 |
220 |
310 |
135*125 |
|
1000A |
400 |
0.014 |
1000 |
290 |
230 |
310 |
|
Note: The above specifications are the company’s standard products, and the product performance, size and appearance can be customized according to the customer’s products.
Product Display
Product detail pictures:
Related Product Guide:
With a positive and progressive attitude to customer's interest, our company continuously improves our product quality to meet the needs of customers and further focuses on safety, reliability, environmental requirements, and innovation of Europe Style For Ac Adapter Transformer - Three phase AC Type input reactor – Xinping , The product will supply to all over the world, such as: Frankfurt, Bangladesh, South Africa, Insisting over the high-quality generation line management and prospects guide provider, we've made our resolution to offer our shoppers using the initially stage purchasing and soon after provider working experience. Preserving the prevailing helpful relations with our prospects, we even now innovate our product lists the many time to meet up with the brand new wants and stick to the latest trend of this business in Ahmedabad. We're ready to facial area the difficulties and make the transform to grasp many of the possibilities in international trade.
We are a small company that has just started, but we get the company leader's attention and gave us a lot of help. Hope we can make progress together!