Factory Outlets For 110vac To 220vac Transformer - Three phase AC Type input reactor – Xinping
Factory Outlets For 110vac To 220vac Transformer - Three phase AC Type input reactor – Xinping Detail:
Characteristic
Effectively restrain harmonic current, improve the power factor of the whole machine, effectively restrain the current impact caused by the sudden change of grid voltage and over-voltage, improve the interference of the power supply to other equipment, and improve the unbalanced voltage between power supply phases that is greater than the rated voltage
| Technical Data | |
| Rated Voltage: | 380V/440V |
| Operation Frequency: | 50/60HZ |
| Rated Current: | 3A-1600A |
| Hi-pot Test: | 3.5kV, 60sec |
| Insulation Class: | F or above |
| Reactor Impedance: | 2% |
| Ambient temperature: | -25^ to 401: |
| Protection Category: | I POO |
| Design corresponding to Standards: | GB19212.1-2008 / GB19212.21-2007 /GB1094.6-2011 |
Application Schematic
Outline dimension drawing

|
Type Selection Table |
|||||||
|
|
|
(mH) |
(A) |
m(m) Dimensions 1 |
|||
|
Model |
Power (KW) |
Inductance |
Rated Current |
L |
W |
H |
Installation dimensions E*F |
|
5A |
1.5 |
2.80 |
5 |
160 |
120 |
140 |
80*60 |
|
7A |
2.2 |
2.00 |
7 |
160 |
120 |
140 |
80*60 |
|
10A |
3.7 |
1.40 |
10 |
160 |
120 |
140 |
80*60 |
|
ISA |
5.5 |
0.93 |
15 |
160 |
120 |
140 |
80*60 |
|
20A |
7.5 |
0.70 |
20 |
160 |
120 |
140 |
80*60 |
|
30A |
11 |
0.47 |
30 |
160 |
120 |
140 |
80*60 |
|
40A |
15 |
0.35 |
40 |
160 |
120 |
140 |
80*60 |
|
50A |
18.5 |
0.28 |
50 |
160 |
130 |
140 |
80*75 |
|
60A |
22 |
0.24 |
60 |
160 |
140 |
140 |
80*85 |
|
80A |
30 |
0.17 |
80 |
190 |
150 |
160 |
80*85 |
|
90A |
37 |
0.16 |
90 |
190 |
150 |
160 |
80*85 |
|
120A |
45 |
0.12 |
120 |
190 |
150 |
160 |
80*95 |
|
150A |
55 |
0.09 |
150 |
225 |
160 |
190 |
120*85 |
|
200A |
75 |
0.07 |
200 |
225 |
160 |
220 |
120*85 |
|
220A |
90 |
0.064 |
220 |
225 |
170 |
220 |
120*95 |
|
250A |
110 |
0.056 |
250 |
225 |
180 |
220 |
120*95 |
|
290A |
132 |
0.047 |
290 |
260 |
160 |
250 |
135*85 |
|
330A |
160 |
0.042 |
330 |
260 |
170 |
250 |
135*95 |
|
390A |
185 |
0.036 |
390 |
260 |
170 |
250 |
135*95 |
|
440A |
200 |
0.032 |
440 |
260 |
170 |
250 |
135*95 |
|
490A |
220 |
0.028 |
490 |
260 |
180 |
250 |
135*95 |
|
540A |
250 |
0.025 |
540 |
290 |
200 |
310 |
135*95 |
|
600A |
280 |
0.023 |
600 |
290 |
210 |
310 |
135*95 |
|
700A |
315 |
0.021 |
700 |
290 |
210 |
310 |
135*105 |
|
800A |
350 |
0.018 |
800 |
290 |
220 |
310 |
135*125 |
|
1000A |
400 |
0.014 |
1000 |
290 |
230 |
310 |
|
Note: The above specifications are the company’s standard products, and the product performance, size and appearance can be customized according to the customer’s products.
Product Display
Product detail pictures:
Related Product Guide:
We are committed to providing easy,time-saving and money-saving one-stop purchasing service of consumer for Factory Outlets For 110vac To 220vac Transformer - Three phase AC Type input reactor – Xinping , The product will supply to all over the world, such as: Bahamas, Jakarta, Jamaica, We integrate design, manufacture and export together with more than 100 skillful workers, strict quality controlling system and experienced technology.We keep long term business relationships with wholesaler and distributors form more than 50 countries, such as USA, UK, Canada, Europe and Africa etc.
As an international trading company, we have numerous partners, but about your company, I just want to say, you are really good, wide range, good quality, reasonable prices, warm and thoughtful service, advanced technology and equipment and workers have professional training, feedback and product update is timely, in short, this is a very pleasant cooperation, and we look forward to the next cooperation!