Technical Data
Rated Voltage: | 400VDC~1000VDC |
Rated Current: | 2A-900A |
Insulation Class: | F or above |
Reactor Impedance: | 2% |
Ambient temperature: | -25℃ to 40℃ |
Protection Category: | I POO |
Design corresponding to Standards: | GB19212.1-2008 / GB19212.21-2007 /GB1094.6-2011 |
Application Schematic
Outline dimension drawing
Type Selection Table
|
|
(mH) |
(A) |
(mm) Dimensions |
|||
Model |
Power (KW) |
Inductance |
Rated Current |
L |
W |
H |
Installation dimensions E*F |
3A |
0.4/0.75 |
28 |
3 |
115 |
130 |
110 |
90*70 |
6A |
1.5/2.2 |
11 |
6 |
115 |
130 |
110 |
90*70 |
12A |
3.7/4.0 |
6.3 |
12 |
115 |
130 |
110 |
90*70 |
23A |
5.5/7.5 |
3.6 |
23 |
115 |
140 |
110 |
90*80 |
33A |
11/15 |
2 |
33 |
115 |
140 |
110 |
90*80 |
40A |
18.5 |
1.3 |
40 |
115 |
150 |
110 |
90*90 |
50A |
22 |
1.08 |
50 |
115 |
160 |
110 |
90*100 |
65A |
30 |
0.8 |
65 |
132 |
165 |
120 |
110*100 |
78A |
37 |
0.7 |
78 |
150 |
170 |
140 |
122*110 |
95A |
45 |
0.54 |
95 |
150 |
170 |
140 |
122*110 |
115A |
55 |
0.45 |
115 |
150 |
180 |
140 |
122*120 |
160A |
75 |
0.36 |
160 |
150 |
160 |
190 |
120*85 |
180A |
90 |
0.33 |
180 |
150 |
170 |
190 |
120*95 |
250A |
110 |
0.26 |
250 |
180 |
190 |
220 |
135*105 |
290A |
132 |
0.22 |
290 |
180 |
195 |
220 |
135*105 |
340A |
160 |
0.17 |
340 |
180 |
200 |
220 |
135*115 |
460A |
185 |
0.09 |
460 |
200 |
190 |
270 |
135*105 |
490A |
220 |
0.08 |
490 |
200 |
195 |
270 |
135*105 |
650A |
300 |
0.07 |
650 |
200 |
200 |
270 |
135*115 |
Note: The above specifications are the company’s standard products, and the product performance, size and appearance can be customized according to the customer’s products.
Product Display
Product detail pictures:

Related Product Guide:
We have now our possess revenue group, design staff, technical crew, QC team and package group. We now have strict excellent regulate procedures for each process. Also, all of our workers are experienced in printing subject for Free Sample For 120 Volt To 24 Volt Dc Transformer - Inverter/servo direct matching DC smoothing reactor – Xinping , The product will supply to all over the world, such as: Brasilia, Toronto, Turkmenistan, With the enterprising spirit of high efficiency, convenience, practicality and innovation, and in line with such serving guidance of good quality but better price, and global credit, we are striving to cooperate with the automobile parts companies all over the world to make a win-win partnership.

Sales manager is very enthusiastic and professional, gave us a great concessions and product quality is very good,thank you very much!