Characteristic
Effectively restrain harmonic current, improve the power factor of the whole machine, effectively restrain the current impact caused by the sudden change of grid voltage and over-voltage, improve the interference of the power supply to other equipment, and improve the unbalanced voltage between power supply phases that is greater than the rated voltage
| Technical Data | |
| Rated Voltage: | 380V/440V |
| Operation Frequency: | 50/60HZ |
| Rated Current: | 3A-1600A |
| Hi-pot Test: | 3.5kV, 60sec |
| Insulation Class: | F or above |
| Reactor Impedance: | 2% |
| Ambient temperature: | -25^ to 401: |
| Protection Category: | I POO |
| Design corresponding to Standards: | GB19212.1-2008 / GB19212.21-2007 /GB1094.6-2011 |
Application Schematic
Outline dimension drawing

|
Type Selection Table |
|||||||
|
|
|
(mH) |
(A) |
m(m) Dimensions 1 |
|||
|
Model |
Power (KW) |
Inductance |
Rated Current |
L |
W |
H |
Installation dimensions E*F |
|
5A |
1.5 |
2.80 |
5 |
160 |
120 |
140 |
80*60 |
|
7A |
2.2 |
2.00 |
7 |
160 |
120 |
140 |
80*60 |
|
10A |
3.7 |
1.40 |
10 |
160 |
120 |
140 |
80*60 |
|
ISA |
5.5 |
0.93 |
15 |
160 |
120 |
140 |
80*60 |
|
20A |
7.5 |
0.70 |
20 |
160 |
120 |
140 |
80*60 |
|
30A |
11 |
0.47 |
30 |
160 |
120 |
140 |
80*60 |
|
40A |
15 |
0.35 |
40 |
160 |
120 |
140 |
80*60 |
|
50A |
18.5 |
0.28 |
50 |
160 |
130 |
140 |
80*75 |
|
60A |
22 |
0.24 |
60 |
160 |
140 |
140 |
80*85 |
|
80A |
30 |
0.17 |
80 |
190 |
150 |
160 |
80*85 |
|
90A |
37 |
0.16 |
90 |
190 |
150 |
160 |
80*85 |
|
120A |
45 |
0.12 |
120 |
190 |
150 |
160 |
80*95 |
|
150A |
55 |
0.09 |
150 |
225 |
160 |
190 |
120*85 |
|
200A |
75 |
0.07 |
200 |
225 |
160 |
220 |
120*85 |
|
220A |
90 |
0.064 |
220 |
225 |
170 |
220 |
120*95 |
|
250A |
110 |
0.056 |
250 |
225 |
180 |
220 |
120*95 |
|
290A |
132 |
0.047 |
290 |
260 |
160 |
250 |
135*85 |
|
330A |
160 |
0.042 |
330 |
260 |
170 |
250 |
135*95 |
|
390A |
185 |
0.036 |
390 |
260 |
170 |
250 |
135*95 |
|
440A |
200 |
0.032 |
440 |
260 |
170 |
250 |
135*95 |
|
490A |
220 |
0.028 |
490 |
260 |
180 |
250 |
135*95 |
|
540A |
250 |
0.025 |
540 |
290 |
200 |
310 |
135*95 |
|
600A |
280 |
0.023 |
600 |
290 |
210 |
310 |
135*95 |
|
700A |
315 |
0.021 |
700 |
290 |
210 |
310 |
135*105 |
|
800A |
350 |
0.018 |
800 |
290 |
220 |
310 |
135*125 |
|
1000A |
400 |
0.014 |
1000 |
290 |
230 |
310 |
|
Note: The above specifications are the company’s standard products, and the product performance, size and appearance can be customized according to the customer’s products.
Product Display
Product detail pictures:
Related Product Guide:
abide by the contract, conforms to the market requirement, joins during the market competition by its superior quality also as provides extra comprehensive and exceptional service for consumers to let them turn into significant winner. The pursue of the business, is definitely the clients' gratification for Massive Selection For 120v Ac To 36v Dc Transformer - Three phase AC Type input reactor – Xinping , The product will supply to all over the world, such as: France, Armenia, kazan, All our staffs believe that: Quality builds today and service creates future. We know that good quality and the best service are the only way for us to achieve our customers and to achieve ourselves too. We welcome customers all over the word to contact us for future business relationships. Our products are the best. Once Selected, Perfect Forever!
Product quality is good, quality assurance system is complete, every link can inquire and solve the problem timely!