Short Lead Time For 120 Volt Ac To 6 Volt Dc Transformer - Three phase AC Type input reactor – Xinping
Short Lead Time For 120 Volt Ac To 6 Volt Dc Transformer - Three phase AC Type input reactor – Xinping Detail:
Characteristic
Effectively restrain harmonic current, improve the power factor of the whole machine, effectively restrain the current impact caused by the sudden change of grid voltage and over-voltage, improve the interference of the power supply to other equipment, and improve the unbalanced voltage between power supply phases that is greater than the rated voltage
| Technical Data | |
| Rated Voltage: | 380V/440V |
| Operation Frequency: | 50/60HZ |
| Rated Current: | 3A-1600A |
| Hi-pot Test: | 3.5kV, 60sec |
| Insulation Class: | F or above |
| Reactor Impedance: | 2% |
| Ambient temperature: | -25^ to 401: |
| Protection Category: | I POO |
| Design corresponding to Standards: | GB19212.1-2008 / GB19212.21-2007 /GB1094.6-2011 |
Application Schematic
Outline dimension drawing

|
Type Selection Table |
|||||||
|
|
|
(mH) |
(A) |
m(m) Dimensions 1 |
|||
|
Model |
Power (KW) |
Inductance |
Rated Current |
L |
W |
H |
Installation dimensions E*F |
|
5A |
1.5 |
2.80 |
5 |
160 |
120 |
140 |
80*60 |
|
7A |
2.2 |
2.00 |
7 |
160 |
120 |
140 |
80*60 |
|
10A |
3.7 |
1.40 |
10 |
160 |
120 |
140 |
80*60 |
|
ISA |
5.5 |
0.93 |
15 |
160 |
120 |
140 |
80*60 |
|
20A |
7.5 |
0.70 |
20 |
160 |
120 |
140 |
80*60 |
|
30A |
11 |
0.47 |
30 |
160 |
120 |
140 |
80*60 |
|
40A |
15 |
0.35 |
40 |
160 |
120 |
140 |
80*60 |
|
50A |
18.5 |
0.28 |
50 |
160 |
130 |
140 |
80*75 |
|
60A |
22 |
0.24 |
60 |
160 |
140 |
140 |
80*85 |
|
80A |
30 |
0.17 |
80 |
190 |
150 |
160 |
80*85 |
|
90A |
37 |
0.16 |
90 |
190 |
150 |
160 |
80*85 |
|
120A |
45 |
0.12 |
120 |
190 |
150 |
160 |
80*95 |
|
150A |
55 |
0.09 |
150 |
225 |
160 |
190 |
120*85 |
|
200A |
75 |
0.07 |
200 |
225 |
160 |
220 |
120*85 |
|
220A |
90 |
0.064 |
220 |
225 |
170 |
220 |
120*95 |
|
250A |
110 |
0.056 |
250 |
225 |
180 |
220 |
120*95 |
|
290A |
132 |
0.047 |
290 |
260 |
160 |
250 |
135*85 |
|
330A |
160 |
0.042 |
330 |
260 |
170 |
250 |
135*95 |
|
390A |
185 |
0.036 |
390 |
260 |
170 |
250 |
135*95 |
|
440A |
200 |
0.032 |
440 |
260 |
170 |
250 |
135*95 |
|
490A |
220 |
0.028 |
490 |
260 |
180 |
250 |
135*95 |
|
540A |
250 |
0.025 |
540 |
290 |
200 |
310 |
135*95 |
|
600A |
280 |
0.023 |
600 |
290 |
210 |
310 |
135*95 |
|
700A |
315 |
0.021 |
700 |
290 |
210 |
310 |
135*105 |
|
800A |
350 |
0.018 |
800 |
290 |
220 |
310 |
135*125 |
|
1000A |
400 |
0.014 |
1000 |
290 |
230 |
310 |
|
Note: The above specifications are the company’s standard products, and the product performance, size and appearance can be customized according to the customer’s products.
Product Display
Product detail pictures:
Related Product Guide:
We now have a skilled, performance team to supply good quality services for our consumer. We often follow the tenet of customer-oriented, details-focused for Short Lead Time For 120 Volt Ac To 6 Volt Dc Transformer - Three phase AC Type input reactor – Xinping , The product will supply to all over the world, such as: Uruguay, Uruguay, Cairo, Only for accomplishing the good-quality product to meet customer's demand, all of our products have been strictly inspected before shipment. We always think about the question on the side of the customers, because you win, we win!
Good quality and fast delivery, it's very nice. Some products have a little bit problem, but the supplier replaced timely, overall, we are satisfied.