Short Lead Time For 120 Volt Ac To 6 Volt Dc Transformer - Three phase AC Type input reactor – Xinping
Short Lead Time For 120 Volt Ac To 6 Volt Dc Transformer - Three phase AC Type input reactor – Xinping Detail:
Characteristic
Effectively restrain harmonic current, improve the power factor of the whole machine, effectively restrain the current impact caused by the sudden change of grid voltage and over-voltage, improve the interference of the power supply to other equipment, and improve the unbalanced voltage between power supply phases that is greater than the rated voltage
| Technical Data | |
| Rated Voltage: | 380V/440V |
| Operation Frequency: | 50/60HZ |
| Rated Current: | 3A-1600A |
| Hi-pot Test: | 3.5kV, 60sec |
| Insulation Class: | F or above |
| Reactor Impedance: | 2% |
| Ambient temperature: | -25^ to 401: |
| Protection Category: | I POO |
| Design corresponding to Standards: | GB19212.1-2008 / GB19212.21-2007 /GB1094.6-2011 |
Application Schematic
Outline dimension drawing

|
Type Selection Table |
|||||||
|
|
|
(mH) |
(A) |
m(m) Dimensions 1 |
|||
|
Model |
Power (KW) |
Inductance |
Rated Current |
L |
W |
H |
Installation dimensions E*F |
|
5A |
1.5 |
2.80 |
5 |
160 |
120 |
140 |
80*60 |
|
7A |
2.2 |
2.00 |
7 |
160 |
120 |
140 |
80*60 |
|
10A |
3.7 |
1.40 |
10 |
160 |
120 |
140 |
80*60 |
|
ISA |
5.5 |
0.93 |
15 |
160 |
120 |
140 |
80*60 |
|
20A |
7.5 |
0.70 |
20 |
160 |
120 |
140 |
80*60 |
|
30A |
11 |
0.47 |
30 |
160 |
120 |
140 |
80*60 |
|
40A |
15 |
0.35 |
40 |
160 |
120 |
140 |
80*60 |
|
50A |
18.5 |
0.28 |
50 |
160 |
130 |
140 |
80*75 |
|
60A |
22 |
0.24 |
60 |
160 |
140 |
140 |
80*85 |
|
80A |
30 |
0.17 |
80 |
190 |
150 |
160 |
80*85 |
|
90A |
37 |
0.16 |
90 |
190 |
150 |
160 |
80*85 |
|
120A |
45 |
0.12 |
120 |
190 |
150 |
160 |
80*95 |
|
150A |
55 |
0.09 |
150 |
225 |
160 |
190 |
120*85 |
|
200A |
75 |
0.07 |
200 |
225 |
160 |
220 |
120*85 |
|
220A |
90 |
0.064 |
220 |
225 |
170 |
220 |
120*95 |
|
250A |
110 |
0.056 |
250 |
225 |
180 |
220 |
120*95 |
|
290A |
132 |
0.047 |
290 |
260 |
160 |
250 |
135*85 |
|
330A |
160 |
0.042 |
330 |
260 |
170 |
250 |
135*95 |
|
390A |
185 |
0.036 |
390 |
260 |
170 |
250 |
135*95 |
|
440A |
200 |
0.032 |
440 |
260 |
170 |
250 |
135*95 |
|
490A |
220 |
0.028 |
490 |
260 |
180 |
250 |
135*95 |
|
540A |
250 |
0.025 |
540 |
290 |
200 |
310 |
135*95 |
|
600A |
280 |
0.023 |
600 |
290 |
210 |
310 |
135*95 |
|
700A |
315 |
0.021 |
700 |
290 |
210 |
310 |
135*105 |
|
800A |
350 |
0.018 |
800 |
290 |
220 |
310 |
135*125 |
|
1000A |
400 |
0.014 |
1000 |
290 |
230 |
310 |
|
Note: The above specifications are the company’s standard products, and the product performance, size and appearance can be customized according to the customer’s products.
Product Display
Product detail pictures:
Related Product Guide:
With sophisticated technologies and facilities, strict top quality handle, reasonable value, exceptional support and close co-operation with clients, we are devoted to furnishing the ideal worth for our clients for Short Lead Time For 120 Volt Ac To 6 Volt Dc Transformer - Three phase AC Type input reactor – Xinping , The product will supply to all over the world, such as: Philippines, Muscat, belarus, We've got constructed strong and long co-operation relationship with an enormous quantity of companies within this business in Kenya and overseas. Immediate and professional after-sale service supplied by our consultant group has happy our buyers. Thorough Info and parameters from the merchandise will probably be sent for you for any thorough acknowledge. Free samples may be delivered and company check out to our corporation. n Kenya for negotiation is constantly welcome. Hope to get inquiries type you and construct a long-term co-operation partnership.